Electromagnetic flow meters (magmeters) are widely used in wastewater treatment due to their non-obstructive design and ability to handle dirty fluids. However, various installation, environmental and operational factors can cause measurement inaccuracies or equipment failure. This guide examines the most common issues and provides practical solutions.

Installation & Commissioning Issues

1. Improper Sensor Positioning

  • Problem Cases:
    • Mounted at pipeline high points (traps air)
    • Vertical downward flow without backpressure
    • Post-meter discharge to atmosphere
  • Effect:
    • Partial pipe filling errors
    • 10-100% measurement deviation
  • Solution:
    • Follow manufacturer’s elevation requirements
    • Install vacuum breakers if needed
    • Use full-bore valves for maintenance

2. Electrical Interference

  • Interference Sources:
    • Stray currents (50-60Hz AC)
    • Variable frequency drives
    • Welding equipment
  • Diagnostic:
    • Fluctuations synchronous with equipment cycles
  • Mitigation:
    • Install grounding rings
    • Use shielded cables (95% coverage minimum)
    • Maintain 3m separation from power lines

3. Fluid Characteristics

  • Bubble Effects:
    • 5% air volume causes signal dropout
    • Foamy streams require conditioning
  • Slurry Challenges:
    • Low-frequency meters susceptible to noise
    • 1-3Hz pulsations common
  • Material Selection:
    • Hastelloy C electrodes for chlorides
    • PTFE liners for abrasive flows

Operational Problems

1. Coating Accumulation

  • Consequence Matrix:
Coating TypeEffectSolution
Insulating (grease)Signal lossMechanical cleaning
Conductive (metal)Short circuitChemical dissolution
MixedUnstable zeroUltrasonic cleaners

Maintenance Tip: Install inspection ports for visual verification

2. Lightning Damage

  • Vulnerable Components:
    • Excitation coils (30% failure rate)
    • Signal converters (45% failure)
  • Protection Measures:
    • Class I surge protectors
    • Fiber optic isolation
    • Lightning arrestors every 50m

3. Environmental Changes

  • New Interference Sources:
    • Substations (<15m distance)
    • Radio transmitters (>5W)
    • Arc furnaces
  • Retrofit Solutions:
    • Upgrade to frequency-agile models
    • Install ferrite filters
    • Implement Faraday cages

Maintenance Best Practices

  • Quarterly:
    • Ground resistance testing (<5Ω)
    • Electrode continuity check
  • Biannual:
    • Liner thickness inspection
    • Full calibration verification
  • Emergency:
    • Post-storm diagnostic scans
    • Coating thickness analysis

Troubleshooting Flowchart

  1. Check for sudden vs gradual deviation
  2. Verify proper grounding
  3. Inspect for coating buildup
  4. Test with known fluid volume
  5. Isolate electrical interference

Conclusion

Proactive maintenance and proper installation can prevent 80% of electromagnetic flow meter issues in wastewater applications. Key strategies include optimal sensor placement, robust electrical protection, and regular coating inspections.

Still haven’t solved the problem? Click for help.